Wire Size Calculator

Auto-select wire size from allowable current and voltage drop — free electrical engineering design tool

Related Categories:Building Services
Circuit Conditions
Single-PhaseThree-Phase
PVCXLPE
ConduitOpen Air
Recommended Wire Size

Selected Size

14mm²

Ampacity: 88A

Voltage Drop

3.69 V

(1.85%)

Limiting Factor

Voltage Drop

By Ampacity

2.6mm

By Voltage Drop

14mm²

Wire Size Ampacity Table
SizeArea (mm²)Ampacity (A)
1.6mm227
2.0mm3.1435
2.6mm5.3148
5.5mm²5.549
8mm²861
14mm²1488
22mm²22115
38mm²38162
60mm²60217
100mm²100298
150mm²150395
200mm²200469
250mm²250556
325mm²325650

Voltage drop formula:

Single-phase: e = 2×ρ×L×I / A

Three-phase: e = √3×ρ×L×I×cosφ / A

ρ(copper) = 1/58 Ω·mm²/m